P0: repair FAT relay-bench runtime latency - #265
Conversation
|
Relay-bench P0 Gate 1 is green at Passed:
Gate 1 repairs report-backed analog Value 1/Value 2 latency and removes per-event physical disk barriers while keeping final journal durability/seal verification. Proceeding to the next isolated gate: fast FAT attach to an already-live shared Engineering Static DataSet/RCB acquisition session. PR remains draft and must not merge before physical relay acceptance. |
|
P0 LIVE VALUE + Command Panel gate completed on
Full CI green:
ARIEC61850 source was not modified; immutable pin remains PR intentionally remains draft. Physical relay-bench Start/capture/Recapture/command/LIVE VALUE acceptance is still required before merge. |
P0 locked-scope verification — LIVE VALUE + stable Command PanelRe-verified the current PR head
Full CI on this exact head is green:
No additional code churn is warranted for this locked P0. PR should remain draft until physical-relay acceptance; P1 remains out of scope until that gate is stable. |
Repair status update — current head
|
P0 software gate complete — exact head
|
P0 relay-bench recovery — software gate complete / physical bench pending
Golden reference remains Build #1888 / ARSAS commit
712e2c557d5da83d2f02b81f3a58905e985d1e50with immutable ARIEC61850 pin11ab2304482600c19ba979f4fc9021ddb46b9af9. This PR is the current-line physical relay-bench candidate; it is not the golden baseline and must not be merged until the bench gate below passes.Current candidate head:
f91abd071a5e14e32fe7fb8c9db7145160e35113.P0 software behavior now locked
Loaded; the first visible frame uses the final schema and canonical BooleanTrue/Falsepresentation.Capturebuttons are removed.FatAutoCaptureCoordinatorowns normal capture; deliberate Snapshot/Recapture remains the operator correction path.Exact-head CI gate — GREEN on
f91abd07Portable candidate:
ARSAS-win-x64-portable-single-exe(9989904684)c642ce76cf324ddfbd84163d589ba5115faa2fce4b93f723510438c3b8af16bbARSAS-1.6.33-win-x64-portable.exe6b98c3bb3f081baaf68f30dbb3b017da55e167b277f12b1f69baa067ff6ba87fPhysical relay-bench acceptance still required
TEST | SIGNAL | IEC REFERENCE | TYPE | LIVE VALUE | VALUE 1 | VALUE 2 | STATUS | RESULT; no legacy ON/OFF or lower-case Boolean flash.Closed → Open → Closedfrom stale MMS verification and must not create phantom SOE; a genuine contradictory report must still appear immediately.Do not merge until this physical relay-bench gate passes.