PS7000 Modbus register map

English · 中文

Read-only Modbus RTU register map and working example clients for the Pisonics PS7000 ultrasonic slurry density meter — a non-nuclear inline density meter that measures acoustic impedance, so it needs no radioactive source, no licence and no disposal route.

Everything here is generated from a single source of truth (registers/input-registers.json) and the decoder is unit tested, so the parts that are easy to get wrong are checked rather than assumed.

Three things that account for most first-day problems

1. Register numbers here are 1-based; the frame address is one lower. To read register 1026, put 1025 in the request. Get it wrong and the block still reads — just shifted by one, giving a plausible but wrong number.

2. 32-bit values are CDAB — low word first. Most masters default to ABCD. If floats decode as denormals or zeros, this is why.

3. Read the block in one request. The firmware publishes a consistent snapshot; field-by-field reads are slower and can mix measurement cycles.

Quick check that you have both right: read register 805. It must return 0x50 (density / concentration meter) or 0x51 (spectral concentration meter). Anything else means you are off by one.

Quick start — Python

cd examples/python
pip install -r requirements.txt
python read_ps7000.py --port /dev/ttyUSB0 --slave 1
             density: 1.4210 g/cm3
   probe temperature: 31.50 degC
      signal quality: 0.930
              loop 1: 11.203 mA
             up time: 86400 s
 entrained gas (EMA): 4 / 100

The decoding lives in ps7000.py, which has no dependencies at all. You can lift that one file into your own project and ignore the rest. Its tests run without an instrument:

python test_ps7000.py

The one field to read

mainValueFilteredregister 1026, F32. Read mainValueUnit (register 1028) alongside it, because the same instrument can be configured to report density in g/cm³ or kg/m³, mass or volume concentration, Baumé, or solids in g/L. A host that assumes one will be wrong by roughly 100× the day someone changes it on the panel.

Is the reading fresh?

Use measureErrorCode (register 1004), not the ok field (register 1029).

ok reports sampling quality for the cycle. On aerated or turbulent slurry it is routinely 0 while the value is perfectly live and the current loop is normal. Code that treats ok == 0 as "frozen" stops acting on alarms exactly when the process gets noisy. Details and the exact bit list are in docs/error-codes.md.

Entrained gas

On SW 4.x the instrument reports an entrained-gas index (registers 1104 and 1113) alongside the density value. It is derived from frame-to-frame variance rather than absolute echo amplitude — which is the point, because amplitude alone cannot separate "more bubbles" from "more solids": both push it the same way. Alarm on the smoothed value (1113); the instantaneous one (1104) spikes on a single bubble crossing the beam.

Scope

This repository covers read-only registers — function code 0x04, the process values and diagnostics a PLC, DCS or historian needs.

Configuration, calibration and control writes are covered by the official Modbus manual supplied with the instrument. If you need it, ask us.

Register numbers are stable from SW 3.3.26 onward. The measurement block is append-only: newer firmware adds fields at the end and never moves an existing one, so a host written against an older map keeps working.

Regenerating the tables

python tools/gen_tables.py

Edit the JSON, never the generated Markdown or CSV.

About Pisonics

Pisonics builds inline density and concentration meters for mining, power generation, chemical processing and dredging. The PS7000 series measures slurry density by acoustic impedance, covering DN50 to DN1000 without a radioactive source.

Questions about integration: info@pisonics.com

Licence

Documentation and register data: CC BY 4.0. Example code: MIT.