Complete list of entities created by the integration, organized by device. The
integration automatically detects your heat pump model and creates devices based
on your system configuration.
For patterns and conventions used to build these entities, see
Entity Patterns.
Gateway Device
Entity
Type
Description
Category
connectivity
binary_sensor
Indicates if the gateway is connected and responding
diagnostic
system_state
sensor
Gateway synchronization state with the heat pump
diagnostic
telemetry_status
sensor
Current telemetry consent level (off/on) with send tracking attributes
diagnostic
Heat Pump Control Unit Device
Controls
Entity
Type
Description
Values
power
switch
Main power switch for the heat pump unit
on/off
operation_mode
select
Operating mode of the heat pump (modes depend on configuration)
heat only, or heat/cool/auto
Temperatures
Entity
Type
Description
Unit
outdoor_temp
sensor
Outdoor ambient temperature measurement
°C
water_inlet_temp
sensor
Water temperature at the heat pump inlet
°C
water_outlet_temp
sensor
Water temperature at the heat pump outlet
°C
water_outlet_2_temp
sensor
Water outlet 2 temperature (Two2, conditional)
°C
water_outlet_3_temp
sensor
Water outlet 3 temperature (Two3, conditional)
°C
water_target_temp
sensor
Corrected target water temperature
°C
System Status
Entity
Type
Description
Category
operation_state
sensor
Current operation state with detailed description
diagnostic
alarm
sensor
Current alarm status
diagnostic
defrost
binary_sensor
Unit is currently in defrost mode
diagnostic
compressor
binary_sensor
Compressor is running
diagnostic
boiler
binary_sensor
Backup boiler is active (if supported)
diagnostic
dhw_heater
binary_sensor
DHW electric heater is active (if DHW configured)
diagnostic
solar
binary_sensor
Solar system is active (disabled by default)
diagnostic
space_heater
binary_sensor
Space heating electric heater is active (disabled by default)
diagnostic
smart_function
binary_sensor
Smart grid function is active (disabled by default)
diagnostic
Hydraulic
Entity
Type
Description
Unit
Category
water_flow
sensor
Current water flow rate through the system
m³/h
diagnostic
pump_speed
sensor
Current speed of the water circulation pump
%
diagnostic
pump1
binary_sensor
Water pump 1 is running (disabled by default)
-
diagnostic
pump2
binary_sensor
Water pump 2 is running (disabled by default)
-
diagnostic
pump3
binary_sensor
Water pump 3 is running (disabled by default)
-
diagnostic
Electrical Energy
Entity
Type
Description
Unit
Category
power_consumption
sensor
Total electrical energy consumed by the unit
kWh
diagnostic
Thermal Energy
Entity
Type
Description
Unit
Category
thermal_power_heating
sensor
Real-time thermal heating power output
kW
diagnostic
thermal_power_cooling
sensor
Real-time thermal cooling power output (cooling circuits only)
kW
diagnostic
thermal_energy_heating_daily
sensor
Daily thermal heating energy (resets at midnight)
kWh
diagnostic
thermal_energy_heating_total
sensor
Total cumulative thermal heating energy
kWh
diagnostic
thermal_energy_cooling_daily
sensor
Daily thermal cooling energy (cooling circuits only)
kWh
diagnostic
thermal_energy_cooling_total
sensor
Total cumulative thermal cooling energy (cooling circuits only)
kWh
diagnostic
Performance (COP)
Entity
Type
Description
Category
cop_heating
sensor
Space heating COP
diagnostic
cop_cooling
sensor
Space cooling COP (cooling circuits only)
diagnostic
cop_dhw
sensor
Domestic hot water COP (if DHW configured)
diagnostic
cop_pool
sensor
Pool heating COP (if pool configured)
diagnostic
Each COP sensor exposes additional attributes: quality, measurements, and
time_span_minutes.
Primary Compressor Device
Entity
Type
Description
Unit
Category
compressor_running
binary_sensor
Compressor is running
-
diagnostic
compressor_frequency
sensor
Operating frequency
Hz
diagnostic
compressor_current
sensor
Electrical current draw
A
diagnostic
compressor_tg_gas_temp
sensor
Gas temperature
°C
diagnostic
compressor_ti_liquid_temp
sensor
Liquid temperature
°C
diagnostic
compressor_td_discharge_temp
sensor
Discharge temperature
°C
diagnostic
compressor_te_evaporator_temp
sensor
Evaporator temperature
°C
diagnostic
compressor_evi_indoor_expansion_valve_opening
sensor
Indoor expansion valve opening
%
diagnostic
compressor_evo_outdoor_expansion_valve_opening
sensor
Outdoor expansion valve opening
%
diagnostic
compressor_cycle_time
sensor
Average time between compressor starts
min
diagnostic
compressor_runtime
sensor
Compressor runtime
min
diagnostic
compressor_resttime
sensor
Compressor rest time
min
diagnostic
Secondary Compressor Device (S80 Model Only)
Entity
Type
Description
Unit
Category
secondary_compressor_running
binary_sensor
Secondary compressor is running
-
diagnostic
secondary_compressor_frequency
sensor
Operating frequency
Hz
diagnostic
secondary_compressor_current
sensor
Electrical current draw
A
diagnostic
secondary_compressor_discharge_temp
sensor
Discharge temperature
°C
diagnostic
secondary_compressor_suction_temp
sensor
Suction temperature
°C
diagnostic
secondary_compressor_discharge_pressure
sensor
Discharge pressure
bar
diagnostic
secondary_compressor_suction_pressure
sensor
Suction pressure
bar
diagnostic
secondary_compressor_cycle_time
sensor
Average time between compressor starts
min
diagnostic
secondary_compressor_runtime
sensor
Compressor runtime
min
diagnostic
secondary_compressor_resttime
sensor
Compressor rest time
min
diagnostic
Circuit Device (up to 2 circuits)
Climate and Controls
Entity
Type
Description
Values
climate
climate
Main climate control entity
off/heat/cool/auto or off/heat_cool
eco_mode
switch
Enable ECO mode (reduced temperatures)
on/off
thermostat
switch
Enable Modbus thermostat function (if available)
on/off
Configuration (disabled by default)
Entity
Type
Description
Values/Unit
Category
otc_calculation_method_heating
select
Heating water temperature calculation method
disabled/points/gradient/fix
config
otc_calculation_method_cooling
select
Cooling water temperature calculation method
disabled/points/fix
config
max_flow_temp_heating_otc
number
Maximum heating water temperature for OTC
°C (0–80)
config
max_flow_temp_cooling_otc
number
Maximum cooling water temperature for OTC
°C (0–80)
config
heat_eco_offset
number
Temperature offset in ECO mode for heating
°C (1–10)
config
cool_eco_offset
number
Temperature offset in ECO mode for cooling
°C (1–10)
config
Service
Service
Description
Fields
hitachi_yutaki.set_room_temperature
Set the room temperature for a circuit
temperature (0–50°C, step 0.1)
Domestic Hot Water Device (if configured)
Entity
Type
Description
Values/Unit
dhw
water_heater
Main DHW control entity
off/standard/high demand, 30–60°C
boost
switch
Temporarily boost DHW production
on/off
antilegionella
button
Manually start a high temperature anti-legionella cycle
-
antilegionella_temp
number
Target temperature for anti-legionella treatment (disabled by default)
°C (60–80)
dhw_demand_mode
sensor
DHW demand mode configured in the heat pump (disabled by default)